Technical data

2. SYSTEM DESCRIPTION
1. SCOPE
CHLORIDE Active
UPS from 700 VA to 3000 VA
MKA4CAT0UKAG4/Rev. 1-07/2008
02
This document describes a continuous electrical power, within defined limits time period defined by the battery
duty single-phase output, on-line double and without interruption, upon failure or system, which will be automatically
conversion uninterruptible power supply degradation of the commercial AC recharged by the UPS upon restoration
(UP S) system. The UPS shall source. The continuity of conditioned of the commercial AC source.
automatically provide continuity of electric power shall be delivered for the
2.1 The system as shown in the figure below, and shall interaction with the standard front
provide the following benefits: panel with LED indicators and the
optional LCD display
High energy efficiency in power
An increasing number of devices are
conversion, including ECO mode Intelligent load management
sensitive to disturbances on the mains
provided by the controllable output
power supply. The Active UPS system Outstanding output power factor
sockets
shall provide high quality AC power for =0,9 (*)
connected equipment and offer the Possibility of operation as frequency
Easy-swappable internal batteries, for
following features: converter
simplified maintenance without
Protection against power failures disconnecting the loads Availability of internal automatic
bypass to keep the load fed in the
Improvement in the power supply Advanced battery management,
event of a UPS failure, reducing
quality increasing battery life
disruption and maximising uptime
Compatibility with all types of load Simplified commissioning, thanks to
Minimization of mains distortions
the auto-detection of external battery
thanks to the enhanced input power
packs
Active shall operate based on DSP-
factor correction.
User-friendly notification and
driven Double Conversion technology,
UPS Model
Active 700T
Active 1000T
Active 1500T
Active 1000RT
Active 1500RT
Active 2000RT
Active 3000RT
Housing
Tower
Tower
Tower
Rack/Tower
Rack/Tower
Rack/Tower
Rack/Tower
Rating (*)
700VA/630W
1000VA/900W
1500VA/1350W
1000VA/900W
1500VA/1350W
2000VA/1800W
3000VA/2700W
Battery Pack
BP-A1000/1500-T
BP-A1000/1500-RT
BP-A2000/3000-RT
Housing
Tower
Rack/Tower
Rack/Tower
Compatible UPS
Active 1000T / Active 1500T
Active 1000RT / Active 1500RT
Active 2000RT / Active 3000RT
(*) These ratings are only valid for the UPS without external battery packs
and considering a nominal voltage of 230 V. Check technical data for
further details.
Active block diagram
Filter
PFC
Charger
Booster
Inverter
Filter
L
N
L
N
E E
+V
-V
-
+
2.2 Models available
The Active product range shall include the following single-phase pluggable models and external battery packs: