Secure Power Always Active from 700 to 3000 VA UPS Catalogue
Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products are for installation, operation and maintenance. Product designations All product designations used are trademarks or product names of Chloride Group PLC or its subsidiary companies. This publication is issued to provide outline information and is not deemed to form any part of any offer or contract.
Uninterruptible Power Supply UPS Catalogue • 2008 Active from 700 VA to 3000 VA 1. SCOPE 2 2. SYSTEM DESCRIPTION 2 3. DEVICE DESCRIPTION 3 4. GENERAL REQUIREMENTS 4 5. BATTERY MANAGEMENT 4 6. CONTROL PANEL 5 7. REAR SIDE 6 8. INTERFACES & CONNECTIVITY 8 9. MECHANICAL DATA 9 10. TECHNICAL DATA 11. OPTIONS 01 9 10 MKA4CAT0UKAG4/Rev.
CHLORIDE Active UPS from 700 VA to 3000 VA 1. SCOPE This document describes a continuous duty single-phase output, on-line double conversion uninterruptible power supply ( U P S ) s ys t e m . Th e U P S s h a l l automatically provide continuity of electrical power, within defined limits and without interruption, upon failure or degradation of the commercial AC source.
CHLORIDE Active UPS from 700 VA to 3000 VA 3. DEVICE DESCRIPTION 3.1 Components/blocks CHARGER The charger includes a temperature compensation which regulates the charging process. When the mains voltage is within tolerances, the charger provides a nominal recharge current up to 1.2A to the batteries. This element is current-limited; therefore, it can only provide the nominal current, although batteries may demand more current. Typical recharge time for internal batteries is 4 hours (for 90% recharge).
CHLORIDE Active UPS from 700 VA to 3000 VA 4. GENERAL REQUIREMENTS 4.1 Standards and certifications 2006/95/EC and the EMC Directive 2 0 0 4 / 10 8 / E C ( s u p e r s e d i n g t h e Chloride operates with a Quality Management System which complies with ISO 9001:2000 for the design, m a n u f a c tu r e , s a l e , i n s t a l l a t i o n , maintenance and service of uninterruptible power supply systems.
CHLORIDE Active UPS from 700 VA to 3000 VA 5. BATTERY MANAGEMENT 2000 VA models UPS UPS + 1BP UPS + 2BP UPS + 3BP UPS + 4BP 320 W 37 min 163 min 236 min 358 min 445 min 800 W 15 min 58 min 109 min 177 min 213 min 1120 W 11 min 40 min 73 min 114 min 166 min 5.
CHLORIDE Active UPS from 700 VA to 3000 VA 6. CONTROL PANEL 6.2 Panel with LCD (optional) Active offers (as an option, focused on advanced users) a multiple language LCD display for complete UPS monitoring and control. The text is available in English, French, German, Italian, Portuguese and Spanish. Complete access to LCD menu is possible through navigation push buttons located below the screen. The LCD panel may be rotated to fit horizontal and vertical mounting.
CHLORIDE Active UPS from 700 VA to 3000 VA 7. REAR SIDE Active Tower 1500 Legend: 1. Communication slot 2. Input circuit breaker 3. Input power socket (10A) 4. Not controllable output sockets (10A) 5. Controllable outlets (2 groups,10A) 6. USB port 7. RS232 port (DB9) 8. Fan 9. External battery pack connection 10. RJ11 port for battery pack detection cable 11. ROO/RPO terminals 12. Earth Screw Battery Pack Active 1000/1500 RT Legend: 1. Battery pack connector 2.
CHLORIDE Active UPS from 700 VA to 3000 VA 8. INTERFACES & CONNECTIVITY Active shall be equipped with DB9 and USB communication ports and a slot for inserting advanced communication cards.
CHLORIDE Active UPS from 700 VA to 3000 VA 9. MECHANICAL DATA 9.1 Enclosure 9.2 Ventilation 9.3 Installation of rack/tower units The UPS shall be housed in an enclosure with removable front panels (UPS internal batteries shall be accessible from the front panel) and IP20 protection. Standard colour of the enclosure shall be RAL7016 (grey anthracite), thus providing an optimum alternative for most environments.
CHLORIDE Active UPS from 700 VA to 3000 VA 10. TECHNICAL DATA CONNECTIONS Input 1 x IEC320 C14 (10A) Output 6 x IEC320 C13 (10A), (2 groups contr.
CHLORIDE Active UPS from 700 VA to 3000 VA 11. OPTIONS 11.3 ManageUPS CIO Active shall be compatible with ManageUPS CIO software. ManageUPS CIO is software for the Management Workstation element in a system for managing UPS and related critical infrastructure in large facilities, campus or enterprise net work environments.
NOTE 12 MKA4CAT0UKAG4/Rev.
www.chloridepower.com Closest Chloride Contact in Australia: Chloride Australia Ground Floor 16 Giffnock St, North Ryde NSW 2113 Australia. Closest Chloride Contact in UAE: Chloride UPS Systems Middle East Building 5, Office 104 Dubai Internet City - Dubai UAE PO Box 72536 Closest Chloride Contact in South East Asia: CHLD Singapore Pte Ltd 2 Corporation Road #03-07 Corporation Place Singapore 618494 T +61 2 9888 1266 F +61 2 9888 1966 E australia.sales@chloridepower.