Technical data

99
99
9
MKA4ST0UKPLAN5-7/Power Lan/ed.5/09-2003/UK
CHLORIDECHLORIDE
CHLORIDECHLORIDE
CHLORIDE
POWER PROTECTION
PIN SIGNAL
1 Reserved (+5V @ 10mA)
2 TXD, transmits data to the PC
3 Ground
4 RXD; receives data from the PC
6.2 Computer interface
The Shutdown connector (RJ11 with 4 wires) provides the following signals:
This connector provides RS-232-level signals required for shutdown. The ground is common with the RS-232
connector. The remote shutdown signal (+12V) should persist for at least 2.5 seconds to be accepted. Cable
42 can be used if volt-free contacts are needed as it provides the mains failure and battery low signals through
volt-free contacts (see Options Section).
6.3 POWER CONTROL CONNECTOR (Remote control and signalling)
The POWER CONTROL connector (SUB-D 25 pin female) provides the following signals:
Pin Use Signal
1 Mains failure Active Closed
2 UPS ON Active Closed
3 Low battery Active Closed
4 Solid-state by-pass ON Active Closed
5 Remote shutdown
14 Signal sink
15 Ground (connected to pin 14)
17 Remote start-up +12V
18 Outputs +15V, 100 mA +15V
PIN SIGNAL
1 Low battery
2 Mains failure
3 Ground
4 Remote shutdown (from a PC)