User`s guide
APPENDIX E: MODBUS REGISTER MAP
913-623 @Rev A Appendix E Page 7
Information available via Modbus
Function Code 03 - Read Holding Registers
All points are unsigned integers
Default MODBUS Offset is 1 (configurable via WEB interface)
Information Supported by UPS Model
Relative
Address
(Default
Modbus
point)
Designation Comment
Linear
Plus
70Net
80Net
90Net
CP3020
CP3150
EDP70,
70L, 90
(Single)
05C0 (93) 3 upsConditionRectifier
(0) Rectifier off
(1) Rectifier turning on
(2) Rectifier on
(3) Rectifier fault
√ √ √ √ √
05Dh (94) 4 upsConditionBatteryConnected
√ 3√ √ √ √ √
05Eh (95) 5 upsConditionNonSynchronism
√ √ √ √ √
060h (96) 6 reserved
061h (97) 7 reserved
062h (98) 8 reserved
063h (99) 9 reserved
064h (100) 10 reserved
upsParallelCondition
065h (101) 1 upsInParallelSet
(0) UPS is single
(1) UPS is part of parallel
set
√ √ √ √ √ √ √
066h (102) 2
upsDetectParallel
Problem
(0)UPS is in single mode
or
runs in parallel mode and
is fine
(1)UPS detects a problem
in parallel mode
√
067h (103) 3 reserved
068h (104) 4 reserved
069h (105) 5 reserved
06Ah (106) 6 reserved
06Bh (107) 7 reserved
customerDedicatedInformation
06Ch (108) 1 customerInfo1
06Dh (109) 2 customerInfo2
06Eh (110) 3 customerInfo3
06Fh (111) 4 customerInfo4
070h (112) 5 customerInfo5
√
071h (113) 3 reserved
072h (114) 4 reserved
073h (115) 5 reserved
074h (116) 6 reserved
075h (117) 7 reserved