User`s guide
APPENDIX E: MODBUS REGISTER MAP
Appendix E Page 6 913-623 @Rev A
Information available via Modbus
Function Code 03 - Read Holding Registers
All points are unsigned integers
Default MODBUS Offset is 1 (configurable via WEB interface)
Information Supported by UPS Model
Relative
Address
(Default
Modbus
point)
Designation Comment
Linear
Plus
70Net
80Net
90Net
CP3020
CP3150
EDP70,
70L, 90
(Single)
058h (89)
bit 0
33 upsAlarmFanFailure
√
√
058h bit 1 34 upsAlarmFuseFailure
√
058h bit 2 35 upsAlarmGeneralFault
√ √ √ √ √ √
058h bit 3 36 upsAlarmDiagnosticTestFailed
√
√
058h bit 4 37 upsAlarmCommunicationsLost
√ √ √ √ √ √ √
058h bit 5 38 upsAlarmAwaitingPower
058h bit 6 39 upsAlarmShutdownPending
√ √ √ √ √ √
058h bit 7 40 upsAlarmShutdownImminent
058h bit 8 41 reserved
058h bit 9 42 reserved
058h bit 10 43 reserved
058h bit 11 44 reserved
058h bit 12 45 reserved
058h bit 13 46 reserved
058h bit 14 47 reserved
058h bit 15 48 reserved
059h (90)
bit 0
49 upsAlarmTestInProgress
√ √ √ √ √ √
059h bit 1 50 upsAlarmAutonomyCalibration
059h bit 2 51 upsAlarmGeneralWarning
√ √ √ √ √ √
059h bit 3 52 upsAlarmBatteryCharging
√
059h bit 4 53 upsAlarmBackfeedRelayFailure
059h bit 5 54 upsAlarmBatteryFuseBlown
059h bit 6 55 upsAlarmSystemRestartPending
059h bit 7 56 upsAlarmBatteryDegraded
059h bit 8 57 reserved
059h bit 9 58 reserved
059h bit 10 59 reserved
059h bit 11 60 reserved
059h bit 12 61 reserved
059h bit 13 62 reserved
059h bit 14 63 reserved
059h bit 15 64 reserved
upsCondition
05Ah (91) 1 upsConditionBypass
(0) Bypass not present
(1) Bypass on
(2) Bypass off
(3) Bypass fault
(4) Bypass not prepared
√ √ √
√ √ √
05Bh (92) 2 upsConditionInverter
(0) Inverter off
(1) Inverter turning on
(2) Inverter on
(3) Inverter fault
(4) Inverter turning off
√
√ √ √ √ √