User`s guide

APPENDIX E: MODBUS REGISTER MAP
913-623 @Rev A Appendix E Page 5
Information available via Modbus
Function Code 03 - Read Holding Registers
All points are unsigned integers
Default MODBUS Offset is 1 (configurable via WEB interface)
Information Supported by UPS Model
Relative
Address
(Default
Modbus
point)
Designation Comment
Linear
Plus
70Net
80Net
90Net
CP3020
CP3150
EDP70,
70L, 90
(Single)
upsAlarm
056h (87)
bit 0
1
upsAlarmsPresent Nb. of active alarms
056h bit 1
2
upsAlarmBatteryBad
056h bit 2
3
upsAlarmOnBattery
056h bit 3
4
upsAlarmLowBattery
056h bit 4 5 upsAlarmDepletedBattery
056h bit 5 6 upsAlarmTempBad
056h bit 6 7 upsAlarmInputBad
056h bit 7 8 upsAlarmOutputBad
056h bit 8 9 reserved
056h bit 9 10 reserved
056h bit 10 11 reserved
056h bit 11 12 reserved
056h bit 12 13 reserved
056h bit 13 14 reserved
056h bit 14 15 reserved
056h bit 15 16 reserved
057h (88)
bit 0
17 upsAlarmOutputOverload
057h bit 1 18 upsAlarmOnBypass
057h bit 2 19 upsAlarmBypassBad
057h bit 3 20 upsAlarmOutputOffAsRequested
057h bit 4 21 upsAlarmUpsOffAsRequested
057h bit 5 22 upsAlarmChargerFailed
057h bit 6 23 upsAlarmUpsOutputOff
057h bit 7 24 upsAlarmUpsSystemOff
057h bit 8 25 reserved
057h bit 9 26 reserved
057h bit 10 27 reserved
057h bit 11 28 reserved
057h bit 12 29 reserved
057h bit 13 30 reserved
057h bit 14 31 reserved
057h bit 15 32 reserved