User`s guide
APPENDIX E: MODBUS REGISTER MAP
913-623 @Rev A Appendix E Page 5
Information available via Modbus
Function Code 03 - Read Holding Registers
All points are unsigned integers
Default MODBUS Offset is 1 (configurable via WEB interface)
Information Supported by UPS Model
Relative
Address
(Default
Modbus
point)
Designation Comment
Linear
Plus
70Net
80Net
90Net
CP3020
CP3150
EDP70,
70L, 90
(Single)
upsAlarm
056h (87)
bit 0
1
upsAlarmsPresent Nb. of active alarms
√ √
√ √ √ √ √
056h bit 1
2
upsAlarmBatteryBad
√
056h bit 2
3
upsAlarmOnBattery
√ √ √ √ √ √ √
056h bit 3
4
upsAlarmLowBattery
√ √ √ √ √ √ √
056h bit 4 5 upsAlarmDepletedBattery
√ √ √ √ √ √ √
056h bit 5 6 upsAlarmTempBad
√ √ √ √ √ √ √
056h bit 6 7 upsAlarmInputBad
√ √ √ √ √ √ √
056h bit 7 8 upsAlarmOutputBad
√
056h bit 8 9 reserved
056h bit 9 10 reserved
056h bit 10 11 reserved
056h bit 11 12 reserved
056h bit 12 13 reserved
056h bit 13 14 reserved
056h bit 14 15 reserved
056h bit 15 16 reserved
057h (88)
bit 0
17 upsAlarmOutputOverload
√ √ √ √ √ √ √
057h bit 1 18 upsAlarmOnBypass
√ √ √ √ √ √ √
057h bit 2 19 upsAlarmBypassBad
√ √ √ √ √ √ √
057h bit 3 20 upsAlarmOutputOffAsRequested
057h bit 4 21 upsAlarmUpsOffAsRequested
√
057h bit 5 22 upsAlarmChargerFailed
√ √ √ √ √ √
057h bit 6 23 upsAlarmUpsOutputOff
057h bit 7 24 upsAlarmUpsSystemOff
√
057h bit 8 25 reserved
057h bit 9 26 reserved
057h bit 10 27 reserved
057h bit 11 28 reserved
057h bit 12 29 reserved
057h bit 13 30 reserved
057h bit 14 31 reserved
057h bit 15 32 reserved