APPENDIX E: MODBUS REGISTER MAP
Appendix E Page 4 913-623 @Rev A
Information available via Modbus
Function Code 03 - Read Holding Registers
All points are unsigned integers
Default MODBUS Offset is 1 (configurable via WEB interface)
Information Supported by UPS Model
Relative
Address
(Default
Modbus
point)
Designation Comment
Linear
Plus
70Net
80Net
90Net
CP3020
CP3150
EDP70,
70L, 90
(Single)
03Dh (62)
13
upsOutputPercentLoad
L1
[%]
03Eh (63)
14
upsOutputPercentLoad
L2
[%]
03Fh (64)
15
upsOutputPercentLoad
L3
[%]
040h (65)
16
reserved
041h (66)
17
reserved
042h (67)
18
reserved
043h (68)
19
reserved
044h (69)
20
reserved
upsBypass
045h (70) 1 upsBypassLineBads
046h (71) 2 upsBypassFrequency [0,1 Hz]
047h (72) 3
upsBypass
InputNumLines
048h (73) 4
upsBypassVoltage L1 [V]
049h (74) 5
upsBypassVoltage L2 [V]
04Ah (75) 6
upsBypassVoltage L3 [V]
V
04Bh (76) 7 upsBypassCurrent L1 [0,1 A]
04Ch (77) 8 upsBypassCurrent L2 [0,1 A]
04Dh (78) 9 upsBypassCurrent L3 [0,1 A]
04Eh (79) 10 upsBypassRealPower L1 [0,1kW]
04Fh (80) 11 upsBypassRealPower L2 [0,1kW]
050h (81) 12 upsBypassRealPower L3 [0,1kW]
051h (82) 13 reserved
052h (83) 14 reserved
053h (84) 15 reserved
054h (85) 16 reserved
055h (86) 17 reserved