User`s guide
APPENDIX E: MODBUS REGISTER MAP
913-623 @Rev A Appendix E Page 3
Information available via Modbus
Function Code 03 - Read Holding Registers
All points are unsigned integers
Default MODBUS Offset is 1 (configurable via WEB interface)
Information Supported by UPS Model
Relative
Address
(Default
Modbus
point)
Designation Comment
Linear
Plus
70Net
80Net
90Net
CP3020
CP3150
EDP70,
70L, 90
(Single)
028h (41) 10 upsInputRealPower L1 [0,1kW]
√
√
029h (42) 11 upsInputRealPower L2 [0,1kW]
√
√
02Ah (43) 12 upsInputRealPower L3 [0,1kW]
√
√
02Bh (44) 13
upsInputDCVoltage [V]
√ √ √ √ √
02Ch (45) 14
reserved
02Dh (46) 15
reserved
02Eh (47) 16 reserved
02Fh (48) 17 reserved
030h (49) 18 reserved
upsOutput
031h (50)
1 upsOutputSource (1) other
(2) none
(3) normal
(4) bypass
(5) battery
(6) booster
(7) reducer
√ √ √ √ √ √ √
032h (51)
2 upsOutputFrequency [0,1 Hz]
√
√ √ √ √ √
√
033h (52)
3 upsOutputNumLines
√
√ √ √ √ √
√
034h (53)
4 upsOutputVoltage L1 [V]
√
√ √ √ √ √
√
035h (54)
5 upsOutputVoltage L2 [V]
√ √ √ √ √
√
036h (55)
6 upsOutputVoltage L3 [V]
√ √ √ √ √
√
037h (56)
7
upsOutputCurrent L1 [0,1 A]
√
√ √ √ √ √
√
038h (57)
8
upsOutputCurrent L2 [0,1 A]
√ √ √ √ √ √
039h (58)
9
upsOutputCurrent L3 [0,1 A]
√ √ √ √ √ √
03Ah (59)
10
upsOutputRealPower L1 [0,1kW]
√
√ √ √ √ √
03Bh (60)
11
upsOutputRealPower L2 [0,1kW]
√ √ √ √ √
03Ch (61)
12
upsOutputRealPower L3 [0,1kW]
√ √ √ √ √