User`s guide

APPENDIX E: MODBUS REGISTER MAP
Appendix E Page 2 913-623 @Rev A
Information available via Modbus
Function Code 03 - Read Holding Registers
All points are unsigned integers
Default MODBUS Offset is 1 (configurable via WEB interface)
Information Supported by UPS Model
Relative
Address
(Default
Modbus
point)
Designation Comment
Linear
Plus
70Net
80Net
90Net
CP3020
CP3150
EDP70,
70L, 90
(Single)
00Eh (15) 13 reserved
00Fh (16) 14 reserved
010h (17) 15 reserved
011h (18) 16 reserved
012h (19) 17 reserved
upsBattery
013h (20) 1 upsBatteryStatus
(1) unknown
(2) batteryNormal
(3) batteryLow
(4) batteryDepleted
014h (21) 2 upsSecondsOnBattery [s]
015h (22) 3
UpsEstimatedSeconds
Remaining
[s]
016h (23) 4
UpsEstimatedCharge
Remaining
[%]
017h (24) 5 upsBatteryVoltage [0,1 V]
018h (25) 6 upsBatteryCurrent [0,1 A]
019h (26) 7 upsBatteryTemperature [°C]
01Ah (27) 8 reserved
01Bh (28) 9 reserved
01Ch (29) 10 reserved
01Dh (30) 11 reserved
01Eh (31) 12 reserved
upsInput
01Fh (32) 1 upsInputLineBads
020h (33) 2 upsInputFrequency [0,1 Hz]
021h (34) 3 upsInputNumLines
022h (35) 4 upsInputVoltage L1 [V]
023h (36) 5 upsInputVoltage L2 [V]
024h (37) 6 upsInputVoltage L3 [V]
025h (38) 7 upsInputCurrent L1 [0,1 A]
026h (39) 8 upsInputCurrent L2 [0,1 A]
027h (40) 9 upsInputCurrent L3 [0,1 A]