User`s guide

APPENDIX E: MANAGEUPS MODBUS REGISTER MAP
913-623 @Rev A Appendix E Page 1
Information available via Modbus
Function Code 03 - Read Holding Registers
All points are unsigned integers
Default MODBUS Offset is 1 (configurable via WEB interface)
Information Supported by UPS Model
Relative
Address
(Default
Modbus
point)
Designation Comment
Linear
Plus
70Net
80Net
90Net
CP3020
CP3150
EDP70,
70L, 90
(Single)
000h (1) not used
upsIdent
001h (2) upsIdentModbus
ProtocolVersion
XX.YY
002h (3) 1 upsIdentManufacturer (0) Chloride
(1) Masterguard
(2) Oneac
(3) Reserved
(4) Reserved
(5) Other
003h (4) 2 upsIdentModel (0) SI/SII
(1) 70-net/C/CP3020
(2) 90-net/SIII/CP3150
(3) Reserved
(4) Reserved
(5) Reserved
(6) Reserved
(7) Reserved
(8) 80Net
(9) Reserved
(15) Series A/Active
(16) Series E/Linear+
004h (5) 3 upsIdentUPSSoftware
1Version
HH Major - LL Minor
005h (6) 4 upsIdentUPSSoftware
1DateYear
006h (7) 5 upsIdentUPSSoftware
1DateMonth
007h (8) 6 upsIdentUPSSoftware
1DateDay
008h (9) 7 upsIdentUPSSoftware
1Code
10HXXXXX code
009h (10) 8 upsIdentUPSSoftware
2Version
HH Major - LL Minor
00Ah (11) 9 upsIdentUPSSoftware
2DateYear
00Bh (12) 10 upsIdentUPSSoftware
2DateMonth
00Ch (13) 11 upsIdentUPSSoftware
2DateDay
00Dh (14) 12 upsIdentUPSSoftware
2Code
10HXXXXX code