User`s guide

APPENDIX D: MANAGEUPS TECHNICAL SPECIFICATIONS
Specifications and
Features
ManageUPS
P-Series
Network Interface
10/100 Base-T Ethernet —
Ethernet Class 1 (DIX) packet format
802.3u Compliant – Compatible w/FastEthernet
full/half duplex
Main Processor
Ethernet Controller
Motorola MCF5208 32 bit uController with
integrated 10/100 Mbps Ethernet media access controller (MAC)
Memory
16MB RAM, 4MB Flash memory
Power
90ma @ 12 VDC
@ 44/88 MHz
Serial Interface
Two RS232 asynchronous serial ports
Base
Regulatory
Complies with FCC Class A emission
CE emission and susceptibility requirements
Blue Bus
Microchip 2515 CAN Controller
Hardware
P-
Series
Modbus
RJ11 port offers RS232, RS422, RS485 Half and Full Duplex Options
Agent
SNMP UPS Agent conforms with SNMPv1 RFCs.
UCD-SNMPd from Berkley OpenSource (BSD) Library
(see Open Source aknowledgements in Chloride-Connectivity-License statement
under COLLECTIVE WORK, THIRD PARTY MODULES and OPEN SOURCE ISSUES)
SNMP
MIB Support
RFC1213 (MIB-II) is supported.
SNMPv1 compatible UPS Agent supports a SNMPv1 translation of RFC1628
Meets the requirements of the upsFullCompliance module defined in RFC1628
Automatic Network
Configuration
DHCP client (RFC2131 & 2136-DDNS) and
Apple Zero-Configuration networking BONJOUR
TM
multicast (mDNS) service.
Network Access
SNMP, HTTP, Telnet, FTP, Mopnet
Network Update
Firmware, OS and Configuration update via FTP, TFTP.
Fault messaging
via SNMP Trap and/or email
Serial Port Sharing
Pass-through serial router allows ManageUPSnet to share a single UPS communications port with
other accessories such as a local diagnostics terminal, PC with UPS software or external modem for
remote diagnostics
Client/Server: Mopnet UPS status server with password authentication:
Supports integration with MopUPS UPS monitoring software.
Network Shutdown
Network Shutdown Controller:
Issues shutdown commandsvia network to RCCMD and MopNSA shutdown agents.
Logging
UPS Data and Event log with WEB-based log viewing utilty.
Network
Configuration
Utility
ManageUPS configuration utility enables automatic discovery, configuration guidance and inventory
management from a Win2000/XP workstation.
Features
OTHER
MODBUS
Services
MODBUS services available via AUX Serial communication port or 10/100 Ethernet port.