User`s guide

APPENDIX B: ALARM DETAIL - UPS CONDITIONS THAT TRIGGER MANAGEUPS MESSAGING
SNMP
Alarm
ID
SNMP MIB OID Ref:
Log Entry &
Condition Email Subject
Probable Cause
6 upsAlarmInputBad Input power is out of limits or not present.
7 upsAlarmOutputBad
SNMP Trap only
An output condition is out of tolerance.
SEVERE! Condition Codes
1 upsAlarmBatteryBad Module Battery Needs
Replacing
UPS Battery needs replacing.
4 upsAlarmDepletedBattery Module Depleted Battery Run time is just about zero.
5 upsAlarmTempBad Module Temperature
Limit was Exceeded
Temperature near the battery is too hot.
8 upsAlarmOutputOverload Module Output Overload Output load power is > 100% of rated capacity.
10 upsAlarmBypassBad Module Bypass Bad The bypass is out of tolerance.
13 upsAlarmChargerFailed Module Charger Failed Battery charger has failed or its fuse has blown.
16 upsAlarmFanFailure Module Fan Failure Fan failure detected.
17 upsAlarmFuseFailure Module Fuse Failure Input circuit breaker is open or charger fuse has blown.
18 upsAlarmGeneralFault Module Requires
Servicing
A UPS fault was detected that is not specifically
identified in the UPS protocol or defined in the standard
MIB.
19 upsAlarmDiagnosticTestFailed Module Diagnostics
Failed
A user initiated test has failed.
20 upsAlarmCommunicationsLost Module Lost
Communications
Adapter has Lost Serial Communications with the UPS.
26* upsAlarmBackfeedRelayFailur
e
Module Backfeed Relay
Failure
Backfeed Relay Failure Detected
27* upsAlarmBatteryFuseBlown Module Battery Fuse
Blown
Battery Fuse failure detected.
29* upsAlarmBatteryDegraded Module Battery Degraded The UPS detects that the Battery may need to be
replaced soon
Module Lost
Communications While
On Battery
Adapter has Lost Serial Communications with the UPS
after the UPS reported an On Battery condition.
no trap
System Load Exceeds
Power Margin
The load reported by the UPS exceeds the user
specified power margin