User`s guide

Configuring the Environment Sensor
Environment Sensor 913-623 @Rev A Section VII, page
7
Output Relay Settings – Help Detail Entries
Name:
A user configurable name given to the output relay.
(These values are the
ouputName objects in the Chloride Power Environment
Sensor MIB)
URL:
A url associated with this device. Must be in the format
'http://hostname'. When this value is set the output name becomes a
link on the environment status page.
(These values are the
outputUrl objects in the Chloride Power Environment
Sensor MIB)
Delay:
This setting determines the number of seconds the
Energize Relay When
conditions must be present before the relay is energized.
Hold:
The number of seconds the relay will be held in the energized state after the
Delay
time has expired. If the Energize Relay When conditions are corrected
before this time is up the relay will de-energize.
An entry of ‘0’ in this field will cause the relay to remain energized for as long as
the event condition(s) that trigger the relay remain active.
Energize Relay When:
Configure the relay to energize when any or all of the selected conditions are
present. Multiple conditions can be selected using the Ctrl key and clicking on
entries in the list box. If no conditions are selected the output relay is disabled.