Specifications
Creating a Floor Plan
3-6 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624)
NOTE
Make sure that all cords and cables are long enough to
reach between their respective components and
connectors. Route all cables out of the way of foot traffic.
Figure 3-3 contains the equipment templates to be used in the site-layout grid.
The site-layout grid in Figure 3-4 represents a room measuring 20 ft. by 25 ft. (6 m by
8m). Note that the minimum room size for the core system components is 8 ft. by 8 ft.
(2.6m by 2.6m). The scale of Figure 3-4 is 1/4-inch (0.64 cm) equals 1 foot (30.5 cm).
In Figure 3-4, outline the room in which you will install your ftServer system. Then,
photocopy and cut out the templates in Figure 3-3 and arrange them to represent your
ftServer configuration. The equipment templates are drawn to the same scale as the
grid page.