Specifications
Selecting a UPS Unit for ftServer Systems
2-8 Stratus ftServer V 2302, V 4304, and V 6308 Systems: Site Planning Guide (R624)
AC Power Connections to Qualified UPS Models
AC input power cords must be hardwired to the qualified UPS models. Table 2-5 lists
how the PDU AC input power cords connect to the qualified UPS models.
WARNING
!
A qualified electrician must supply and hardwire the
UPS AC input cord, and if required an AC output cord,
distribution panel, or conduit to each UPS unit in
compliance with local and national electrical code.
Table 2-5. UPS to PDU AC Power Cords for Qualified UPS Models
UPS Model UPS to PDU Power Cord
Chloride - LT081XAT-0H8SX The A-side and B-side PDU AC input cords plug
into L6-20R receptacles on the A-side and B-side
UPS units respectively.
Chloride - LT081XIT-0E3KX Use two B52700-45V power cords for the A-side
and B-side PDU AC input cords. These cords plug
into the IEC C19 receptacles on the A-side and
B-side UPS units respectively.
Chloride - LT081XJT-0H0SX The A-side and B-side PDU AC input cords plug
into L6-20R receptacles on the A-side and B-side
UPS units respectively.
APC - SYH4K6RMT and SYA8K16RMP The A-side and B-side PDU AC input cords plug
into L6-20R receptacles on the A-side and B-side
UPS units respectively.
APC - SYH4K6RMI, SYA8K16RMT, and
SYA8K16RMI
Use two B52700-45V power cords for the A-side
and B-side PDU AC input cords. These cords plug
into the IEC C19 receptacles on the A-side and
B-side UPS units respectively.
APC - SYH4K6RMJ and SYA8K16RMJ The A-side and B-side PDU AC input cords plug
into L6-20R receptacles on the A-side and B-side
UPS units respectively.