B-6 Stratus ftServer V 100, V 200, and V 400 Systems: Site Planning Guide (R543)
Figure B-5 illustrates a three-phase 208-VAC, Y-, or -source circuit connection, which
is a phase-to-neutral source connection. Note that the ftServer system X input can be
connected from L1, L2, or L3. This application requires a single-pole circuit breaker.
Figure B-5. Three-Phase 208-VAC, Y-, or -Source Circuit Connection, Phase-to-Neutral
Circuit A or B
XYG (PE)
To power input A or B
Wall
Power cord
L1
L2
L3
N
G (PE)
120V
120V
208V
208V
120V
0V
Single system: 20A maximum
PDU: 30A maximum