Specifications
PDU Specifications
A-12 Stratus ftServer V 100, V 200, and V 400 Systems: Site Planning Guide (R543)
Table A-8 lists the power cables that connect the V 100 system’s PDU to a UPS.
Table A-9 lists the power cables that distribute power from the PDUs to the V 100
system components.
Table A-10 lists the specifications for the AAP41104V PDU.
Table A-8. Cables From AAP41104V PDUs to a UPS
Cable Part Number
United States, domestic NEMA L6-20 to IEC-320 C19, 208V,
15 ft (4.5m)
AW-B50155-45M
Japan, NEMA L6-20 to IEC-320 C19, 200V, 15 ft (4.5m) AW-B50155-45M
International, IEC-320 C14 to IEC-320 C19, 230V 3.5m AW-B38003
Table A-9. AAP41104V PDU Power Jumper Cords
Power Jumper Cord
Description
Connector
Types Length Marketing ID
Grey 10A 250V C13 to C14 6.56 ft. (2.0m) B50502-02M
Black 10A 250V C13 to C14 6.56 ft. (2.0m) B50503-02M
Table A-10. AAP41104V PDU Specifications (Page 1 of 2)
Power
Output wattage N/A
Nominal input voltage;
Frequency range
200–240 volts AC; 50–60 Hz
Physical Dimensions
Height 1.75 in. (4.45 cm)
Width 19.1 in. (48.51 cm)
Depth 6.75 in. (17.15 cm)
Environmental
Operating temperature during
operation
41
F to 95 F (5 C to 35 C)
For every 800 ft. (243.8m) above 2,000 ft. (609.6m),
lower the maximum operating temperature (35
C) by
1C.