Specifications
Backplane and Enclosures
A-8 Stratus ftServer V 100, V 200, and V 400 Systems: Site Planning Guide (R543)
Environmental Requirements
Operating temperature 41
F to 95F (5C to 35C)
For every 800 ft. (243.8m) above 2000 ft. (609.6m), lower the
maximum operating temperature (95F/35C) by 1.8F (1C)
Storage temperature -38
F to 140F (-40C to 60C)
Operating altitude 0 ft. to 10,000 ft. (0m to 3048m)
Maximum rate of temperature
change during operation
18F/hr. (10C/hr.) or 0.30F/min. (0.17C/min.)
Relative humidity during operation 20% to 80% (noncondensing)
Relative humidity during storage 8% to 80% (noncondensing)
Heat dissipation 3500 BTUs per hour
CPU Enclosure Features
Processors One Intel
Xeon processor in each CPU enclosure.
Memory Six dual data rate (DDR) inline memory module (DIMM) slots in
each CPU enclosure
Up to 6 gigabytes (GB) logical memory
I/O Enclosure Features
Ports One embedded 10/100/1000-Mbps Ethernet port on each core
I/O enclosure
Two AC power connectors and two serial ports
PCI slots Six user-configurable PCI adapter slots:
– One 32-bit 33MHz slot in each core I/O enclosure
– Two 64-bit 33MHz slots in each core I/O enclosure
Table A-3. ftServer V 100 System Specifications (Page 2 of 2)