Specifications
Power Cord Summary
AC Power Planning 2-11
WARNINGWARNING
!
Place all power cords out of the way of foot traffic.
Main Cabinet Ground Cables
Table 2-11 provides information about the main cabinet ground cable.
Table 2-10. Power Cords
Component Power Cord
UPS (Chloride model qualified
by Stratus)
220 VAC input - Customer supplied (hardwired to UPS AC input
terminals)
220 VAC output - See Table 2-5
UPS (APC model qualified by
Stratus)
220 VAC input - Customer supplied (hardwired to UPS AC input
terminals)
220 VAC output - See Table 2-6
PDU for V 200 and V 400
systems
220 VAC input cord permanently attached to PDU - See
Table A-4
220 VAC output. Detachable jumper cords from PDU output
receptacles to system component input receptacles - See
Table A-6
PDU for V 100 systems 220 VAC removable input cord attaches to PDU - See Table A-8
220 VAC output. Detachable jumper cords from PDU output
receptacles to system component input receptacles - See
Table A-9
Expansion storage-system
components
E124 storage-system cabinet. AC source to power strips in
cabinet - See the Stratus ftServer Systems Peripherals Site
Planning Guide (R582)
Table 2-11. Main Cabinet Ground Cable
Component Cable Description Stratus PN Length
Cabinet ground
leakage cable
10AWG ground leakage cable with
1/4 in. (6.35 mm) and M8 ring lugs
AW002000 15 ft (4.6m)