Specifications

Selecting a UPS Unit for ftServer V 200 and V 400 Systems
2-6 Stratus ftServer V 100, V 200, and V 400 Systems: Site Planning Guide (R543)
For UPS specifications, documentation, and ordering information, see APC at
http://www.apcc.com.
V 200 and V 400 AC Power Connections to Qualified UPS Models
AC input power cords must be hardwired to the qualified UPS models. Table 2-5 lists
how the ftServer system PDU AC input cords connect to qualified UPS models.
International No E124 expansion
storage-system cabinets
Two SYA8K16RMI 5600
With one E124 expansion
storage-system cabinet
Two SYA12K16RMI 8400
With two E124 expansion
storage-system cabinets
Two SYA16K16RMI 11200
Japan No E124 expansion
storage-system cabinets
Two SYA8K8RMJ (with
SYPD3 backplate kit)
5600
With one E124 expansion
storage-system cabinet
Two SYA12K16RMJ
(with SYPD3 backplate
kit)
8400
With two E124 expansion
storage-system cabinets
Two SYA16K16RMJ
(with two SYPD3
backplate kits)
11200
† For ftServer V 200 or V 400 system with up to three four-way CPU enclosures, four fully
populated I/O enclosures, one dual tape-drive enclosure, and two fully populated D910 FC
disk enclosures.
Table 2-4. Qualified APC UPS Models for ftServer V 200 or V 400 Systems
Region or
Country
ftServer V 200 or V 400
System Configuration
UPS Quantity and
Model Number
Power Output of
One UPS (Watts)