Specifications

Selecting a UPS Unit for ftServer V 200 and V 400 Systems
2-4 Stratus ftServer V 100, V 200, and V 400 Systems: Site Planning Guide (R543)
Multiply each entry in the Watts Subtotal column by 3.41 and enter the number of
BTUs in the BTUs/hr. Subtotal column.
Determine the total number of BTUs per hour by adding the values in the BTUs/hr.
Subtotal column.
Selecting a UPS Unit for ftServer V 200 and V 400 Systems
Stratus does not sell or service UPS units. However, Stratus has qualified UPS models
for use with ftServer V 200 and V 400 systems.
Each 38U cabinet (with or without expansion storage-system cabinets) uses two UPS
units: one to supply power to the A-side power distribution system and one for the
B-side. Stratus does not supply the UPS units. You must purchase them directly from
the UPS vendor.
Table 2-2. Work Sheet for AC Power and HVAC Requirements
Product Purchased Quantity Watts
Watts
Subtotal
Convert
to BTUs
BTUs/hr.
Subtotal
ftServer V 200 or
V 400 systems main
cabinet
† Value for V 200 and V 400 systems is for a configuration that includes three four-way
CPU enclosures, four fully populated I/O enclosures, one dual tape-drive enclosure,
and two fully populated D910 FC disk enclosures.
x 3150 = x 3.41 =
V 100 systems main
cabinet
‡ Value for V 100 systems is for a configuration that includes two CPU enclosures, two
fully populated core I/O enclosures, one single tape-drive enclosure, and two fully
populated D910 FC disk enclosures.
x 1950 = x 3.41 =
Optional network I/O
enclosure (fully
loaded)
x 750 = x 3.41 =
Additional D910 FC
disk enclosures (fully
populated) in E124
expansion
storage-system
cabinet
x 363 = x 3.41 =
Total BTUs/hr.
Total watts