Specifications
AC Power and HVAC Worksheets
AC Power Planning 2-3
Determine the total number of AC outlets by adding the values in the Subtotal of
AC Outlets column.
In Table 2-2, determine the watts of AC power required by the system and its BTU
output. For each row:
Fill in the Quantity value and multiply it by the supplied Watts value.
Write the result in the Watts Subtotal column.
Determine the total number of watts of AC power required by adding the values in
the Watts Subtotal column.
Table 2-1. Site Planning Worksheet for AC Outlets and Cord Lengths
Product
Purchased
Quantity of
Product
Purchased
No. of AC
Outlets
Required
Subtotal
of AC
Outlets
Type of
Plug
AC Cord
Lengths
Main cabinet
(two PDU AC
power cords
for each
ftServer
system)
——0
†
† Each PDU in the main cabinet connects to a UPS unit.
NEMA L6-30P,
NEMA L6-20P,
IEC60309 30A,
IEC60320-C20P,
or hardwire to
AC output
terminals. See
Tables 2-5, 2-6,
and 2-9 for
details.
V 200 and V 400
United States and
Japan – 12 ft.
V 100 United States
and Japan – 15 ft.
V 200 and V 400
International – 12 ft.
V100 International –
15 ft.
UPS units
(two for each
ftServer
system)
x 1 = Hardwire power
cord with plug
that matches
site receptacles
to UPS
Provided by customer
E124
expansion
storage-syste
m cabinet
x 2 = See the Stratus
ftServer
Systems
Peripherals Site
Planning
Guide (R582)
See the Stratus
ftServer Systems
Peripherals Site
Planning
Guide (R582)
Total AC
connectors