Technical data

9. Technical Data
25
REV: 16/03/01
Operating Manual
945012.066
Models 600 900 1200 1600
INPUT
Nominal voltage
Voltage range
Frequency
Vac
Vac
Hz
230/115
180-285 (ver. 230V) / 90-142 (ver. 115V9
50/60
±
4% automatic selection
OUPUT
Nominal voltage
Voltage regulation
Frequency
Vac
Hz
230/115
198-258 (ver. 230V) / 98-128 (ver.115)
50/60 (see input frequency)
Power VA
W
600
360
900
540
1200
720
1600
960
Power factor 0.6
INVERTER
Wave factor
Nominal voltage
Crest factor
Transfer time
Frequency
Vac
Ms
Hz
Regulated pseudosenoidal
230/115
3:1
<4
50/60
±
0,1 %
BATTERY
Technology Hermetic lead, maintenance-free
13,6 27,2Floatation voltage
Charger current
Vdc
A
0,8 1,7
Recharge time for 80%
Battery test
H <6
Programmable/Automatic/Manual
SIGNALES & COM
DB15 RS-232 serial communication
"Network failure " and “Low battery” (RS-232 configurable logic)
"Shutdown" initiation signal
OTHER
Working temperature
Relative humidity
Maximum altitude
without degradation
ºC
%
m
0 to 40
90 without condensation
3000
mm 155x105x345 170x140x345 308x140x365
Dimensions
(height-width-depth)
Weight
Kg 10 14,5 23
Protection level IP21
CERTIFICATES
EN52091-1 (Ver. 230 V)
EN50091-2 (Ver. 230 V)
UL 1778 (ver. 115 V)
IEEC 062.41 Cat. A
The company reserves the right to changes thes specifications without prior notice.