Installation manual

Iris Touch 400 Range Dialer Installation Manual6
6. Plug in the external cables
Plug the dialer cable into the alarm panel dialer. If the alarm panel has
screw connections, cut the connector off the cable and strip the cable
using the 2 inner wires. Polarity is not important.
Plug the Ethernet cable into the local IP router or socket that has been
allocated for the IP connection.
7. Plug in the sense resistors
Fit the 18K sense resistor in parallel with the dialer output of the alarm
panel, at the alarm panel end of the cable.
Note: This resistor enables the IRIS dialer to detect cable faults and/or
tampers and must be fitted at the alarm panel end of the cable to function
correctly.