Installation manual

IRIS Touch 400 Range Dialler Installation Manual V1.4
14
Appendix A Settings menu
Setting
Purpose
Network Interfaces
Selects which network interfaces are going to be used (i.e.
Ethernet and/or Ethernet/GPRS). Stops dialler reporting trouble
on interfaces not being used.
Account Name/Number
The IRIS account number/name, as allocated by the monitoring
centre.
ARC IP Address
IP address of the receiver at the monitoring centre.
Dialler IP Address
IP address of the dialler, i.e. either automatic (DHCP) or fixed.
GPRS Settings
Diagnostic tools for viewing signal strength and running network
scan. Setting of GPRS Access Point Name (APN), user name
and password, SIM PIN, GSM Call Barring and Roaming SIM.
Alarm Panel Interface
Selects whether or not the 2-wire cable to the dialler is
monitored for short and open circuit.
Note: For monitoring to function correctly a sense resistor must
be fitted as described earlier in this manual.
Sets reporting of poll failure (by dropping line voltage),
simulation of dial tone and cadence of incoming ring signal.
Setting for use with GSM/PSTN only (i.e. no IP) operation.
Setting for serial port emulations.
Alarm Override
If enabled, alarm panel dialled number and account number
overridden by IRIS settings.
Extra Features
Settings for EN54-21, VdS and ILKA operation.
Incoming IP Address
Up to 3 source IP addresses against which incoming TCP/IP
calls can be validated. There will be no validation if all 3 are
clear.
Pin Inputs
Selects whether or not pin inputs are monitored (using sense
resistors) and selects input function:
Send SMS message.
Send SIA, Contact ID and Fast Format alarms over
IP.
Trouble Reporting
Selects how local communications problems are reported, via:
Relay outputs.
SMS.
Sets IP address of support centre for remote diagnostics.
Relay sma activation
Activation of relay outputs by incoming SMS messages.
Language
Selects language.
Installer Password
Sets a password to the Installer menus, if required.
Contrast
Sets display contrast.
Restore
Clears tamper alarm if tamper switches have been triggered.