Data Sheet
NL210 Residual Current 
Operated Circuit Breaker 
without over-current protection
1.3 Approvals and certificates
1.1 Function
Control electric circuits.
Protect people against indirect contacts and additional 
protection against direct contacts.
Protect installations against fire hazard due to insulation 
faults.
Residual current circuit breakers are used in housing, tertiary 
sector and industry.
1.2 Selection
Detectable wave form
Type B
Tripping is ensured for sinusoidal AC residual currents pulsed 
DC residual currents, alternating residual sinusoidal currents 
up to 1000Hz, pulsating direct residual currents and for 
smooth direct residual currents, whether applied suddenly or 
increasing slowly.
 Tripping sensitivity
30mA - additional protection against direct contact.
100mA - co-ordinated with the earth system according to 
the formula IΔn<50/R, to provide protection against indirect 
contacts; 
300mA - protection against indirect contacts, as well as fire 
hazard. 
 Tripping time
Instantaneous
It ensures instantaneous tripping (without time-delay).
CE, KEMA
1.4 Add-on devices
AX-5 auxiliary contacts
TC-1 terminal cover
A
P-036
Modular DIN Rail Products
MCCB
1. General