Specifications

43
Model
CPS
SC1.5KTL
CPS
SC2KTL
CPS
SC2.8KTL
CPS
SC4KTL
CPS
SC4KTL-O
Operational voltage range
7
(F/W Setting)
212~256V
Step1 : 207~246V
S
tep2 : 189~256V
-
Disconnection time of
excess operational voltage
range
1.5 sec.
U/V st1 200.1V(87%), 2.5s
O/V st1 253V(110%), 1s
U/V st2 184V(80%), 0.5s
O/V st2 264.5V(115%), 0.5s
-
Operational frequency
range
8
(F/W Setting)
47.05~50.45Hz
St1 47.55~51.45Hz
St2 47.05~51.95Hz
-
for United
Kingdom
(UK)
Disconnection time of
excess operational
frequency range
0.5 sec.
U/F st1 47.5Hz, 20s
O/F st1 51.5Hz, 90s
U/F st2 47Hz, 0.5s
O/F st2 52Hz, 0.5s
-
7 Regulation voltage range is 207~264 VAC according to G83/1-1
Regulation voltage range is 184V-264.5VAC according to G59 Issue 2
8 Regulation frequency range is 47~50.5Hz according to G83/1-1.
Regulation frequency range is 47~52Hz according to G59 Issue 2