Specifications
25
Auto Test Setting (Only for ENEL GUIDE 2010 model)
The Inverter is supplied with an auto test function which enables the user to
check that the protection interface is operating correctly. In order to select
this function, press the function button until the message "AUTO TEST SET"
appears on the display panel. Press and hold the same button for at least 5
seconds to initiate the auto test procedure.
Press function button until Auto test set appears.
Press and hold function button for more than 5s.
Upper voltage threshold will be checked.
Display shows variation between upper voltage threshold
and mains supply.
If the threshold and the grid voltage are equal, the PV
Inverter switches to fault.
Display shows a message similar to this witch-off time OK.
Lower voltage threshold will be checked.
Display shows variation between lower voltage threshold
and mains supply.