It can be overlooked that the flue must maintain distances from combustibles as well
as the stove.
If the room size is limited you are likely to need to consider heat shielding the length
of the single skinned flue (refer to heat shielding section).
Once in double skinned flue the distance to combustibles are reduced, see table
below.
3.10 Flue distance to combustibles
Single skinned flue Distance to combustibles =
3 x diameter of flue
Max length for single walled flue is
1800mm
Double skinned flue Distance to combustibles =
50-75mm depending on flue
manufacturer
As flue exits the ceiling /roof/wall it must be double skinned
See installation diagrams 3.11