Itispossibletoreducethedistancestocombustibleswithanappropriateheatshield,
(BritishStandard8303).
Wemanufactureseveralsizesofwallmountedheatshieldmadefrom1.5mmsteelwhich
maintainsa40mmairgap.(ThisisgreaterthattheminimumdistancerequiredbyBS8303).
Theyhaveanopentopandbottomtoallowforaowofcoolairbetweentheheatshieldand
combustiblematerial.Beawarethatyouareheatshieldingboththestoveanduecollar.
3.k Heat Shielding
Distances to combustibles, square into corner & flat wall installation 5kW
Thedistancestocombustiblescanbereducedtoaminimumof95mmfrom
therearofthestovetothefrontoftheheatshield,wheninstalledsquare
intoacorner.Thisappliestofreestandinginstallationsonaatwallaswell,
(seediagramonfacingpage).
Distances to combustibles, diagonal corner installation 5kW
Ifthestoveisinstalledatanangleof45degreestothewall,thenthedistance
canbereducedtoaminimumof65mmfromthenearestpointofthestoveto
thefrontfaceoftheheatshield,(seediagramonfacingpage).
FREE STANDING STOVES, 5kW
3.i CO Alarms
Buildingregulationsrequirethatwheneveraneworreplacementxedsolidfuelorwood/
biomassapplianceisinstalledinadwellingacarbonmonoxidealarmmustbettedinthe
sameroomastheappliance.Furtherguidanceontheinstallationofthecarbonmonoxide
alarmisavailableinBSEN50292:2002andfromthealarmmanufacturer’sinstructions.
Provisionofanalarmmustnotbeconsideredasubstituteforeitherinstallingtheappliance
correctlyorensuringregularservicingandmaintenanceoftheapplianceandchimneysystem.
3.j Flue Dampers
Werecommendthatdampersarenotusedwithourstoves.