CP-250E-60/72-208/240-MC4 - User Manual

Installation and Operation Manual
Chilicon Power | Aug 2016
9
THREE PHASE 208 VOLT WIRING
The maximum number of inverters per 208-V split-phase string is 13. There are three power
conductors in a split phase installation. Strings should be staggered across these 3 conductors,
with a third conductor (neutral) to reference the mid-voltage of any 2 of the 3 power
conductors. Chilicon Power trunk cables have 3 color coded conductors, these are: RED, BLACK,
. The CP-250 microinverter system uses the BLACK and conductors for
communication. The inverters automatically detect when they are connected to a 3-phase grid
and the user does not need to provide any additional configuration control.
The Chilicon Power 3-phase gateway option accepts three lines, neutral, and ground. In a 3
phase installation, strings should be configured to connect {L1,L2,N} to {Black,Red, };
{L3,L1,N} to {Black,Red, }; and {L2,L3,N} to {Black,Red, } as shown in the figure
below.
NOTE: Miss-wiring AC grid lines to the inverter trunk (for instance swapping a GRID L1 for GRID
NEUTRAL) will not damage the inverters. However, they cannot export power in this
configuration. If inverters are miss-wired, single blink export confirmation from the LED will not
be established.
WARNING: NEVER CONNECT GREEN to a Live Wire
L3 Bus
N Bus
L2 Bus
L1 Bus
L3
L2
L2
L1
L3
L1
20A / 208 V
J Box
J Box
J Box
Solar AC Subpanel
12 AWG
20A / 208 V
12 AWG
20A / 208V
12 AWG
Max 13 / String
GRID NEUTRAL  WHITE
GRID L1  BLACK Conductor (PLC Phase)
GRID L2  RED Conductor
GROUND  GREEN Conductor
GRID NEUTRAL  WHITE
GRID L1  BLACK Conductor (PLC Phase)
GRID L3  RED Conductor
GROUND  GREEN Conductor
GRID NEUTRAL  WHITE
GRID L2  BLACK Conductor (PLC Phase)
GRID L3  RED Conductor
GROUND  GREEN Conductor