CP-250E-60/72-208/240-MC4 - User Manual
Installation and Operation Manual
Chilicon Power | Aug 2016
9
THREE PHASE 208 VOLT WIRING
The maximum number of inverters per 208-V split-phase string is 13. There are three power
conductors in a split phase installation. Strings should be staggered across these 3 conductors,
with a third conductor (neutral) to reference the mid-voltage of any 2 of the 3 power
conductors. Chilicon Power trunk cables have 3 color coded conductors, these are: RED, BLACK,
. The CP-250 microinverter system uses the BLACK and conductors for
communication. The inverters automatically detect when they are connected to a 3-phase grid
and the user does not need to provide any additional configuration control.
The Chilicon Power 3-phase gateway option accepts three lines, neutral, and ground. In a 3
phase installation, strings should be configured to connect {L1,L2,N} to {Black,Red, };
{L3,L1,N} to {Black,Red, }; and {L2,L3,N} to {Black,Red, } as shown in the figure
below.
NOTE: Miss-wiring AC grid lines to the inverter trunk (for instance swapping a GRID L1 for GRID
NEUTRAL) will not damage the inverters. However, they cannot export power in this
configuration. If inverters are miss-wired, single blink export confirmation from the LED will not
be established.
WARNING: NEVER CONNECT GREEN to a Live Wire
L3 Bus
N Bus
L2 Bus
L1 Bus
L3
L2
L2
L1
L3
L1
20A / 208 V
J Box
J Box
J Box
Solar AC Subpanel
12 AWG
20A / 208 V
12 AWG
20A / 208V
12 AWG
Max 13 / String
GRID NEUTRAL WHITE
GRID L1 BLACK Conductor (PLC Phase)
GRID L2 RED Conductor
GROUND GREEN Conductor
GRID NEUTRAL WHITE
GRID L1 BLACK Conductor (PLC Phase)
GRID L3 RED Conductor
GROUND GREEN Conductor
GRID NEUTRAL WHITE
GRID L2 BLACK Conductor (PLC Phase)
GRID L3 RED Conductor
GROUND GREEN Conductor