CP-250E-60/72-208/240-MC4 - User Manual

Installation and Operation Manual
Chilicon Power | Aug 2016
8
WIRING FOR COMMUNICATION TO THE GATEWAY (240 V SPLIT-PHASE SYSTEMS)
Chilicon Power trunk cables have 4 color-coded conductors: RED, BLACK, , GREEN
BLACK and conductors are for the PLC communication. The same grid line (BLACK) must
be used to connect the inverter to the Gateway to ensure robust communication. Specifically,
the Gateway inside the home (120 V) should be powered using GRID HOT LINE B (= BLACK
trunk conductor) and GRID NEUTRAL (= trunk conductor).
NOTE: Communication with the Gateway is usually fine even if the Gateway is connected in the
wall socket to the RED and trunk-equivalent wires. However, the signal will be weaker.
The Gateway socket survey screen (Menu->Advanced Settings) indicates the strength of the
signal. In the worst case, you simply have to swap the RED and BLACK trunk wires on the
breaker or at the AC disconnect.
NOTE: Miss-wiring AC grid lines to the inverter trunk (for instance swapping a GRID L1 for GRID
NEUTRAL) will not damage the inverters. However, they will not export power in this
configuration. If inverters are miss-wired, LED single blink export confirmation from the LED will
never be established.
WARNING: NEVER CONNECT GREEN to a Live Wire
N Bus
L2 Bus
L1 Bus
L2
L1
L2
L1
L2
L1
20A / 240 V
J Box
J Box
J Box
Solar AC Subpanel
12 AWG
20A / 240 V
12 AWG
20A / 240 V
12 AWG
Max 15 / String
GRID NEUTRAL  WHITE
GRID L2  BLACK Conductor (PLC Phase)
GRID L1  RED Conductor
GROUND  GREEN Conductor
GRID NEUTRAL  WHITE
GRID L2  BLACK Conductor (PLC Phase)
GRID L1  RED Conductor
GROUND  GREEN Conductor
GRID NEUTRAL  WHITE
GRID L2  BLACK Conductor (PLC Phase)
GRID L1  RED Conductor
GROUND  GREEN Conductor