CABLE MAXIMUMS
The maximum size current protection device allowed by NEC code for use with 12AWG wire in
the trunk cable is 20A. This leads to the following calculations for the maximum number of
allowed inverters per trunk cable.
A. Maximum number of inverters on a 20 amp, 240V circuit:
250W output mode: (20A/(1.04*1.25)) = 15
285W output mode: (20A/(1.18*1.25)) = 13 (if 285W enabled by gateway)
B. Maximum number of inverters on a 20 amp, 208V circuit:
250W output mode: (20A/(1.20*1.25)) = 13
285W output mode: (20A/(1.37*1.25)) = 11 (if 285W enabled by gateway)
C. Portrait Mode Installations In portrait mode installations, the maximum supplied trunk
cable length (15 taps) is 15.5m = 51’.
D. Landscape Mode Installations In landscape format installations, the maximum supplied
trunk cable length (15 taps) is 25.5m = 84’