AC Coupling with Microinverter Systems
September 1, 2016
[GRID INTERACTIVE ADVANCED FEATURES]
A
From the Power Management and Control Settings menu, click “Settings”.
The program the required minimum consumption, 0 Watts is the default, placing a larger value creates more margin
to grid-backfeed events. 200 Watts is a reasonable number to use. In addition, make sure the check box ‘Avoid Net
Production’ is selected. The system will no continually program the microinverters, based on the Gen5 HEM net
meter information to prevent backfeed. You can also select ‘Shutdown if no connection’ if it is desired the