Specifications

48 59
Defrost (only applicable to the heating mode)
1. the intelligent defrost
In the heating mode, the electric control board checks and compares the temperature of indoor room and indoor
coil pipe after the compressor works for a while; judge whether the outdoor heat exchanger part is frosted or not
according to conditions such as the change of indoor coil pipe temperature; if it is judged as frosted, it automatically
enters defrosting process. When defrosting, close the indoor and outdoor blower fan and four-way valve.
2. Outdoor PCB for defrost.
In the heating mode, the unit defrost by outdoor control board
unit start defrost shall all meet the following conditions
acompressor continuous running over 7 minutes
bdefrost relay shut off-5
ccompressor cumulate running time over 50 minutes.
first defrost interval time is 50 minutes, later defrost interval time decided by last defrost time.
Defrost
time(minute)
Next defrost interval
time(minute)
15 30
10--15 40
7--10 60
3--7 70
3 80
2end defrost condition(meet one of follows)
adefrost time have fifteen minutes.
bdefrost relay turn on(>8
cpress ON/OFF key in defrost process.
3. Outdoor sensor for defrost
unit start defrost shall meet one of the following conditions
compressor cumulate running time over 30 minutes and it continuous running over 3 minutes, the temperature of
coil pipe of the outdoor units is equal to or less than 15 for one minutes (Tp2 -15 ).
compressor cumulate running time over 40 minutes and it continuous running over 3 minutes, the temperature of
coil pipe of the outdoor units is equal to or less than 5 for one minutes (Tp2 -15 ).
Air conditioner first power on or it wait over 30 minutes ,the temperature of coil pipe of the outdoor units is
equal to or less than 2 (Tp2 -15 )
end defrost condition (meet one of follows)
The temperature of coil pipe of the outdoor units is more than 15 (Tp2 -15 ).
Defrost time has fifteen minutes.