Specifications

54 59
display at
off state
SEC at off
state
signal normal.
2Check whether the signal outputting from
the integrated chip of the electric control
board is normal, the electric control board
should be replaced when the signal is
abnormal.
E7
display at
off state
flicker 7/9
SEC
display
at off
state
outdoor
feedback fault
1Check whether the winding resistance and
operation current of the compressor are
normal
2Check whether the high and low pressure
is normal when the unit is running.
3Check whether the indoor and outdoor
wiring is right; when it is wrong, connect
them again according to the circuit
diagram
4 Check whether the contact of the
inserter on the circuit board and the
connection are well, otherwise repair.
5Check whether the signal feedback wire is
disconnected, replace or connect the
feedback signal wire.
6Check whether the supply power is
phase-lacking or phase opposition.
7Check whether the AC electromagnetic
contactor is well.
E8
display at
off state
flicker 8/10
SEC
display
at off
state
frost
protection/over
heat protection
1Check whether the filter of the indoor unit
is dirty or blocked, and clean if it is dirty.
2Check whether the indoor fan is running
normally, and replace the motor if it is
abnormal.
3Check whether indoor pipe temperature
sensor is normal, and replace the sensor
if it is abnormal.
4Check whether the system pressure is
normal, if abnormal, should check
whether there is leakage, and fill the
refrigerant again.