Specifications

53 59
state
the normal temperature 25), when it is
abnormal the sensor should be replaced.
2Check whether there is short circuit or
open circuit in the wire of the sensor, and
whether the plug is connected well,
whether there is welding off or rosin joint
on the electric control board, if there is
any, it should be repaired.
3When the 1 and 2 are both normal, then
the components or integrated circuit is
damaged, the electric control board
should be replaced.
E4
display at
on/off
state
flicker 4/6
SEC
display
at off
state
outdoor unit
abnormal
1 Check whether the winding resistance
and operation current of the compressor
are normal.
2Check whether the high and low pressure
is normal when the unit is running.
3Check (whether the coil pipe sensor is
normal) whether the contact of the
inserter on the circuit board is well, the
coil pipe temperature sensor is fixed, the
evaporation of the indoor unit is well, the
key is to check the evaporator
temperature detected by the coil pipe
temperature sensor has reached the
cooling or heating temperature.
4 Check whether the surface of the
condenser is too dirty, it should be
cleaned when it is too dirty.
5 Check whether the capacitance of the
outdoor motor and the fan is damaged, it
should be replaced when it is damaged.
6If the above items are normal, the electric
control board should be replaced.
E5
PG
motor
display at
off state
flicker 5/7
SEC
display
at off
state
no feedback
signal of indoor
fan
1Check whether two sets of plugs on the
outlet end of the motor have loosed from
the socket of the electric control board,
insert it firmly when loosing.
2Check whether the indoor motor has
damaged, the motor should be replaced
when it is damaged
3 Check whether the controllable silicon
and other components on the electric
control board have damaged, replace the
controllable silicon or electric control
board when they are damaged.
E6 PG motor flicker 6/8 display no over zero
1Firstly check whether the indoor fan is