Service manual
31 
the  key  is  to  check  the  evaporator  temperature 
detected by the coil pipe temperature sensor has 
reached the cooling or heating temperature. 
4、Check whether the surface of the condenser is too 
dirty, it should be cleaned when it is too dirty. 
5、Check whether the capacitance of the outdoor motor 
and the fan is damaged, it should be replaced when 
it is damaged. 
6、If the above items are  normal,  the  electric  control 
board should be replaced. 
E5 
  PG motor 
display at 
off state 
flicker 5/7 
SEC 
display at 
off state 
  no feedback 
signal of indoor 
fan 
1、Check whether two sets of plugs on the outlet end of 
the motor have loosed from the socket of the 
electric control board, insert it firmly when loosing. 
2、Check whether the indoor motor has damaged, the 
motor should be replaced when it is damaged 
3、 Check whether the controllable silicon and other 
components on the electric control board have 
damaged, replace the controllable silicon or electric 
control board when they are damaged. 
E6 
PG motor 
display at 
off state 
flicker 6/8 
SEC 
display at 
off state 
  no over zero 
signal   
1、Firstly check whether the indoor fan is normal. 
2、Check whether the signal outputting from the 
integrated chip of the electric control board is 
normal, the electric control board should be 
replaced when the signal is abnormal. 
E7 
display at 
off state 
flicker 7/9 
SEC 
display at 
off state 
outdoor 
feedback fault 
1、Check whether the winding resistance and operation 
current of the compressor are normal 
2、Check whether the high and low pressure is normal 
when the unit is running. 
3、Check whether the indoor and outdoor wiring is 
right; when it is wrong, connect them again 
according to the circuit diagram 
4、 Check whether the contact of the inserter on the 
circuit board and the connection are well, otherwise 
repair. 
5、Check whether the signal feedback wire is 










