Service manual

31
the key is to check the evaporator temperature
detected by the coil pipe temperature sensor has
reached the cooling or heating temperature.
4Check whether the surface of the condenser is too
dirty, it should be cleaned when it is too dirty.
5Check whether the capacitance of the outdoor motor
and the fan is damaged, it should be replaced when
it is damaged.
6If the above items are normal, the electric control
board should be replaced.
E5
PG motor
display at
off state
flicker 5/7
SEC
display at
off state
no feedback
signal of indoor
fan
1Check whether two sets of plugs on the outlet end of
the motor have loosed from the socket of the
electric control board, insert it firmly when loosing.
2Check whether the indoor motor has damaged, the
motor should be replaced when it is damaged
3 Check whether the controllable silicon and other
components on the electric control board have
damaged, replace the controllable silicon or electric
control board when they are damaged.
E6
PG motor
display at
off state
flicker 6/8
SEC
display at
off state
no over zero
signal
1Firstly check whether the indoor fan is normal.
2Check whether the signal outputting from the
integrated chip of the electric control board is
normal, the electric control board should be
replaced when the signal is abnormal.
E7
display at
off state
flicker 7/9
SEC
display at
off state
outdoor
feedback fault
1Check whether the winding resistance and operation
current of the compressor are normal
2Check whether the high and low pressure is normal
when the unit is running.
3Check whether the indoor and outdoor wiring is
right; when it is wrong, connect them again
according to the circuit diagram
4 Check whether the contact of the inserter on the
circuit board and the connection are well, otherwise
repair.
5Check whether the signal feedback wire is