Service manual

25
3
80
2end defrost condition(meet one of follows)
adefrost time have fifteen minutes.
bdefrost relay turn on(>8℃)
cpress ON/OFF key in defrost process.
3. Outdoor sensor for defrost
unit start defrost shall meet one of the following conditions
a. compressor cumulate running time over 30 minutes and it continuous running over 3 minutes, the
temperature of coil pipe of the outdoor units is equal to or less than 15 for one minutes (Tp
2
-15).
b. compressor cumulate running time over 40 minutes and it continuous running over 3 minutes, the
temperature of coil pipe of the outdoor units is equal to or less than 5 for one minutes (Tp
2
-15).
c. Air conditioner first power on or it wait over 30 minutes ,the temperature of coil pipe of the outdoor units is
equal to or less than 2 (Tp
2
-15)
end defrost condition(meet one of follows)
a. the temperature of coil pipe of the outdoor units is more than 15 (Tp
2
-15).
b. defrost time have fifteen minutes.
compr essor
out door
bl ower f an
door
bl ower f an
TP2
Tr