ILS Open Plus Exit Antenna Installation: Appendix 1-29
8 Click System Parameters > CFG10 General and configure the following options:
Figure 1.27
System Parameter CGF10 Configuration
•
To tune, activate ISO-Host mode.
9 Click Write to save the configuration.
10 Click System Parameters > CFG15 Antenna Multiplexing and configure the
following options:
Figure 1.28
System Parameter CGF15 Configuration
11
Click to enable Multiplexing and configure the following parameters:
• Switching Condition - after no response
• Number of Input Channels - 1 Input (Single Mode)
• MUX-Valid Time - 20 x 5 ms
• Number of Output Channels => 2
12 Click Write to save the configuration.