1-28 ILS Open Plus 3.0 Installation Manual
4 Click Reader Parameters > CFG3: RF Interface and configure the following
options:
Figure 1.25
RF Interface Configuration
•
In the Transponder-Drivers area, select ISO 15693.
• In the RF Power are, set the power to 8W.
5 Click Write to save the configuration.
6 Click Transponder Parameters > CFG8 General and configure the following
options:
Figure 1.26
Transponder Configuration
•
Datacoding - 1 of 4
• MOD - 10%
• SUB-CARRIER - ASK
• DATA-RATE - High
• NO-TS - 1 Timeslot
• AFI - Disabled
Note: National RF regulations may require different settings.
7 Click Write to save the configuration.