Instruction Manual

Trident Model PD765 Universal Input Meter Instruction Manual
58
Meter Cloning Instructions
NOTICE!
Do not connect the two meters to
the same 4-20 mA loop while
cloning. Internal calibration may
be affected.
1. Connect the two meters using cable assembly PDA7420 or equiva-
lent (e.g. Digi-Key P/N H1663-07-ND). Cable should not exceed
7' (2.1 m).
2. Power up both meters. Leave Clone meter in Run Mode.
3. Enter the Advanced features menu of the Master meter, see Ad-
vanced Features Menu, page 50.
4. Scroll to Copy function using Up arrow button then press
Enter/Ack.
5. The meter displays the message Send. Press Enter/Ack, the dis-
play flashes while sending data. The message done is displayed
when copying is completed.
Copy send
Advanced
Features
done
Display
Flashes While
Sending
Press
Menu
to Exit and
Return to Run Mode
6. The Clone meter displays the memory address being programmed
then the message done when copying is completed. The meter ini-
tializes and returns to Run Mode using the same settings as the
Master.
7. If meter to be cloned does not respond to the data being sent, refer
to Copy Function Requirements above.