Setting Fail-Safe Operation
The fail-safe operation is set independently for each relay. Select
on to
enable or select
off to disable fail-safe operation.
FLSF
FLS1
FLS2
on oFF
Press
Enter/Ack
button to accept setting
Press
Menu
button to exit at any time
on oFF
Programming Time Delay
The On and Off time delays may be programmed for each relay be-
tween 0 and 199 seconds. The relays will transfer only after the condi-
tion has been maintained for the corresponding time delay.
The On time delay is associated with the set point.
The Off time delay is associated with the reset point.
dLAY
dLy1
dLY2
On1 OFF1
Program On
Time Delay
Program Off
Time Delay