Instruction Manual

Trident Model PD765 Universal Input Meter Instruction Manual
36
rLY1 rLY2
FLSF
rELY
dLAY
Act1
SEt1
rSt1
FLS1
FLS2
dLy1
dLY2
Same
Functions as
Relay 1
From Setup
Menu
Press Enter/Ack button to access any menu
Press Menu button to exit at any time
brek
brk1
brk2
Setting the Relay Operation (rely)
This menu allows you to set up the operation of the relays:
1. Relay action
a. Automatic reset only (non-latching)
b. Automatic + manual reset at any time (non-latching)
c. Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm condi-
tion has cleared)
e. Pump alternation control (automatic reset only)
f. Off (relay and status LED disabled)
2. Set point
3. Reset point
4. Fail-safe operation
a. On (enabled)
b. Off (disabled)
5. Time delay
a. On delay (0-199 seconds)
b. Off delay (0-199 seconds)
6. Break Condition Behavior
a. Off (non-alarm condition)
b. On (alarm condition)
Refer to page 24 for a
description of Display
Functions and Messa
g
es