Isolated 4-20 mA Transmitter Output
OUTPUT RANGE 1.00 to 23.00 mA typical
CALIBRATION Factory calibrated for 4-20 mA
SCALING RANGE 0.00 to 23.99 mA for any display range,
see output range above
ACCURACY ± 0.1% FS ± 0.004 mA
TEMPERATURE
DRIFT
0.4 uA/°C from 0 to 65°C ambient
Note: Analog output drift is separate from input drift.
ISOLATED
TRANSMITTER
POWER SUPPLY
One or two transmitter power supplies (Optional)
P1: 24 VDC ± 10% @ 200 mA max. (-1 option)
P1 & P2: 24 VDC ± 10% @ 200 mA & 40 mA max. (-2 option)
EXTERNAL LOOP
POWER SUPPLY
35 VDC maximum
OUTPUT LOOP
RESISTANCE
Power supply Minimum Maximum
24 VDC
10 Ω 700 Ω
35 VDC (external)
100 Ω 1200 Ω
Serial Communications
METER
ADDRESS
PDC protocol: 0 - 99
Modbus protocol: 1 - 247
BAUD RATE 300 – 19,200 bps
TRANSMIT
TIME DELAY
Programmable between 0 and 199 ms
DATA 8 bit (1 start bit, 1 stop bit)
PARITY None (1 or 2 stop bits), even, or odd
(Modbus only; PDC protocol does not use parity)
BYTE-TO-BYTE
TIMEOUT
0.01 – 2.54 sec (Modbus only)
TURN AROUND
DELAY
Less than 2 ms (fixed)
Refer to PDC and Modbus Serial Communication Protocol manuals for
details. These can be downloaded from: www.predig.com.