Data Sheet
TEST
SITE
Ω
H S
E
R
E-3P
0
Insulation
Loop
Earth 3p
RCD
Continuity
Earth Neutral Phase
100 %
0 %
62 %
COMPLEMENTARY FUNCTIONS AVAILABLE ON THE C.A 6133
Automatic test sequence
Save time! The AUTO-RCD automatic test sequence performs the
following operations:
- the No-Trip test, the Trip test at 1 x IΔn and the Trip test at 5 x IΔn,
- if necessary, the Trip test in ramp mode. A single press on the backup
buttons saves all the tests performed.
Another automatic test sequence is also available which performs the
following tests, successively:
LOOP – RCD – INSULATION
The data storage function can be used
to store your measurement results: up
to 99 tests per site on up to 30 sites!
The ANDROID IT-Report application can be used to
transfer the test results stored in the C.A 6133 onto a
tablet or smartphone via Bluetooth. Test reports are
then generated and sent automatically by email or
simply stored for processing later on.
Data storage
Bluetooth communication for Android IT-Report application
Current measurement
CHECK THE COMPLIANCE OF ELECTRICAL INSTALLATIONS WITH A SINGLE INSTRUMENT
3-pole cable for direct measu-
rements on 2P+E sockets.
PASS/FAIL LED for viewing the results
instantaneously.
The MN73A clamp is recognized auto-
matically when it is connected, as is the
measurement calibre.