User manual
22
3. CHARACTERISTICS
3.1. ENVIRONMENTAL CONDITIONS
Indoor use.
Operating range ‑10 °C to +55 °C and 10 % to 85% RH
Storage range ‑40 °C to +70 °C and 10 % to 90% RH
Degree of pollution 2
Altitude < 2000 m
3.2. CONSTRUCTION SPECIFICATIONS
MN93 and MN93A
Dimensions (L x W x H) 135 x 51 x 30 mm
Cord 3,50 metres long
Weight approx. 290 g
C193
Dimensions (L x W x H) 216 x 111 x 45 mm
Cord 3,50 metres long
Weight approx. 690 g
PAC93
Dimensions (L x W x H) 236.5 x 97 x 44 mm
Cord 3,50 metres long
Weight approx. 540 g
Battery life 120 hours with an alkaline battery
AmpFLEX
TM
A193 450 mm
Dimensions (L x W x H) approx. 170 x 158 x 25 mm
Cord 3,50 metres long
Weight approx. 220 g
AmpFLEX
TM
A193 800 mm
Dimensions (L x W x H) approx. 280 x 265 x 25 mm
Cord 3,50 metres long
Weight approx. 270 g
Protection index IP 40 for the clamps and IP 30 jaws open, according to IEC 60 529
IP 65 for the AmpFLEX
TM
according to IEC 60 529
IK 04 according to IEC 50102
Drop test According to IEC 61010‑1
3.3. CONFORMITY TO INTERNATIONAL STANDARDS
Electrical safety according to IEC 61010‑2‑032.
Maximum appliable voltage:
MN93 and MN93A: 600 V Cat III or 300 V Cat IV
C193: 1000 V Cat III or 600 V Cat IV
PAC93: 600 V Cat III or 300 V Cat IV
AmpFLEX: 1000 V Cat III or 600 V Cat IV