2. OPERATION
Forclampswithseveralranges,settheswitchtothehighestrange.
Connecttheclamptothemeasuringinstrument.
If it is not possible to power down the installation, the clamp must be set up and withdrawn in
strictcompliancewiththeapplicablesafetyinstructions.
Theclampmustalwaysbeconnectedtoameasuringinstrumentbeforeenclosingaconductor.
Opentheclamp’sjawsbybringingthearmsclosertogether.Enclosetheconductor(s)carryingthe
currenttobemeasured.Closethejawsbylightlyclickingthemtogether.
For optimum measurement quality, centre the conductor as precisely as possible in the middle
ofthejaws.Makesuretheconductorisperpendiculartothejaws.
Asfaraspossible,keepawayfromotherconductorswhichcouldgeneratespuriouselds.
ReadthemeasurementontheinstrumentandapplythereadingcoefcienttothemeasurementinA
ac
.
Clamp Coefcient
D30NetD30CN x3,000
D31N 500A
ac
range x500
1,000A
ac
range x1,000
1500A
ac
range x1500
D32N 1,000A
ac
range x1,000
2,000A
ac
range x2,000
3,000A
ac
range x3,000
D33N x600
D34N 500A
ac
range x100
1,000A
ac
range x200
1500A
ac
range x300
D35N 1,000A
ac
range x200
2,000A
ac
range x400
3,000A
ac
range x600
D36N x1,000
If necessary, withdraw the clamp from the conductor, change the range and then reposition on the
conductor.
Whenyouhavenishedmeasuring,removetheclampfromtheconductorandthendisconnectthe