Appendix - "Bus analysis" mode
129
12.8.3. Measure (Ethernet 100Basse-T)
Diagnosis
Use this table to troubleshoot problems on a measurement :
Measurement
Description
Diagnosis
Vout
Positive pulse amplitude measurement
Termination problem
Junction connection (oxidation, bad contact, etc.)
Cable length not compliant with standard
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
Time Rise
Rise time between 10% and 90% of a positive
signal amplitude
Unsuitable or damaged cable (the rise and fall
times increase with the cable impedance)
…
Time Fall
Fall time between 90% and 10% of a
negative signal amplitude
DCD
Measurement of the duty cycle between
positive and negative pulses
Measurements taken using a total of the
positive and negative pulses
Unsuitable or damaged cable
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
Cable length not compliant with standard
…
JitterPtoP
Measurement made using the positive and
negative pulses
•
Significant noise (check the cable route, ground braid not
connected, faulty chassis-ground, etc.)
…
Over+
Overshoot measurement on positive pulses.
The max. pulse overshoot is compared to its
amplitude
Unsuitable cable impedance
Termination problem (if there is no termination,
major overshoot and the opposite if the bus
impedance is too high)
Significant noise (check the cable route, ground
braid not connected, faulty chassis-ground, etc.)
…
Over-
Overshoot measurement on negative pulses.
The max. pulse overshoot is compared to its
amplitude.