15.3.5. CURRENT SENSOR CHARACTERISTICS (AFTER LINEARIZATION)
Sensor errors are offset by a typical correction inside the device. This typical correction, applied to the phase and amplitude,
depends on the type of sensor connected (detected automatically) and the gain in the current acquisition channel used.
The RMS current measurement error and phase error are additional errors (which must therefore be added to the device errors),
indicated as influences on the calculations carried out by the analyser (powers, energies, power factors, tangents, etc.).
Type of sensor RMS current (Arms) Maximum error for Arms
Maximum error for Φ
AmpFLEX™ A193
6500 A / 10 kA
[10 A ; 100 A[ ±3 % ±1°
[100 A ; 10 kA] ±2 % ±0.5°
MiniFLEX MA193
6500 A / 10 kA
[10 A ; 100 A[ ±3 % ±1°
[100 A ; 10 kA] ±2 % ±0.5°
AmpFLEX™ A193
100 A
[100 mA ; 100 A] ±3 % ±1°
MiniFLEX MA193
100 A
[100 mA ; 100 A] ±3 % ±1°
J93 clamp
3500 A
[3 A ; 50 A[ - -
[50 A ; 100 A[ ±(2 % + 2.5 A) ±4°
[100 A ; 500 A[ ±(1.5 % + 2.5 A) ±2°
[500 A ; 2000 A[ ±1 % ±1°
[2000 A ; 3500 A] ±1 % ±1.5°
]3500 A ; 5000 A] DC ±1 % -
C193 clamp
1000 A
[1 A ; 10 A[ ±0.8 % ±1°
[10 A ; 100 A[ ±0.3 % ±0.5°
[100 A ; 1000 A] ±0.2 % ±0.3°
PAC93 clamp
1000 A
[1 A ; 10 A[ ±(1.5 % + 1 A) -
[10 A ; 100 A[ ±(1.5 % + 1 A) ±2°
[100 A ; 200 A[ ±3 % ±1.5°
[200 A ; 800 A[ ±3 % ±1.5°
[800 A ; 1000 A[ ±5 % ±1.5°
]1000 A ; 1300 A] DC ±5 % -
MN93 clamp
200 A
[200 mA ; 500 mA[ - -
[500 mA ; 10 A[ ±(3 % + 1 A) -
[10 A ; 40 A[ ±(2.5 % + 1 A) ±3°
[40 A ; 100 A[ ±(2.5 % + 1 A) ±3°
[100 A ; 200 A] ±(1 % + 1 A) ±2°
MN93A clamp
100 A
[100 mA ; 1 A[ ±(0.7 % + 2 mA) ±1.5°
[1 A ; 100 A] ±0.7 % ±0.7°
E3N clamp (10 mV/A)
100A
[100 mA ; 40 A[ ±(2 % + 50 mA) ±0.5°
[40 A ; 100 A] ±7.5 % ±0.5°
E3N clamp (100 mV/A)
10A
[10 mA ; 10 A] ±(1.5 % + 50 mA) ±1°
Clamp MN93A
5 A
[5 mA ; 50 mA[ ±(1 % + 100 µA) ±1.7°
[50 mA ; 500 mA[ ±1 % ±1°
[500 mA ; 5 A] ±0.7 % ±1°
5 A adapter
Essailec
®
adapter
[5 mA ; 50 mA[ ±(1 % + 1.5 mA) ±1°
[50 mA ; 1 A[ ±(0.5 % + 1 mA) ±0°
[1 A ; 5 A] ± 0.5 % ±0°